Electric Power ›› 2017, Vol. 50 ›› Issue (7): 180-184.DOI: 10.11930/j.issn.1004-9649.2017.07.180.05

• Power System • Previous Articles    

Analysis on the High Transmission Tower's Transient Characteristic Caused by Lightning Stroke Considering the Impact of Equivalent Radius

XIONG Junhui1, WANG Zhongyi2, WANG Peng2, LIU Xingting2, ZHAO Yang2   

  1. 1. Nanchang Power Suppty Company, State Grid Jiangxi Power Company, Nanchang 330002, China;
    2. College of Electrical Engineering, Xi'an Jiaotong University, Xi'an 710049, China
  • Received:2017-01-10 Online:2017-07-05 Published:2017-07-25

Abstract: The transient process caused by lightning stroke to the top of high transmission tower is of great importance in the design of the application of the transmission line, line insulator and arrester. In this paper the existing surge impedance models for transmission towers home and abroad are introduced in brief, to improve the model, on this basis the tower body is divided into different pieces, considering the impact of equivalent radius and then analysis the influence of lightning propagation. Through the contrastive analysis of the segments of the tower, the lighting current waveform, and the amplitude of lighting current, and surge impedance effect on the transient characteristic of the tower, combining theoretical analysis, from which we can find that the subdivision of the tower will reduce the overvoltage and prolong the transient process. The conclusion is available for reference to the design of high transmission tower.

Key words: tower, surge impedance model, lighting, transient analysis

CLC Number: