Comparison and Experiment Analysis of Two Simplified Load-Pressure Models of Subcritical Units

ZHANG Ruifeng1, LI Xiaojun1, PAN Hua1, TIAN Liang2   

  1. 1. Guizhou Electric Power Test & Research Institute, Guiyang 550002, China;
    2. Department of Automation, North China Electric Power University, Baoding 071003, China
  • Received:2015-07-19 Online:2015-11-25 Published:2015-10-25
  • Supported by:
    This work is supported by National Basic Research Program of China (973 Program) (No. 2012CB215203).

Abstract: In this paper, the comparison between two simplified nonlinear load-pressure models is conducted for common subcritical units. The theoretical and data analysis show that the difference between the two models, is that the transfer function of load-pressure versus fuel quantity in Model 1 has non-minimum phase characteristics and can preferably fit the pressure difference between drum and throttle pressures. By transplanting the real coordinated control logics into the Matlab software and based on the simulation of the two models, the cotroller parameters are tuned and reset in the real coordianted control system. The result shows that Model 1 outperforms Model 2 substantially, and its control performance is greatly improved compared to the orginal parameters.

Key words: thermal generating unit, load-pressure model, coordinated control