Contrastive Study on Corona Characteristics of Aluminum Conductor Composite Core and Aluminum Conductor Steel Reinforced

GENG Jianghai1, ZHOU Songsong1, QI Xiaomei2   

  1. 1. Hebei Provincial Key Laboratory of Power Transmission Equipment Security Defense, North China Electric Power University, Baoding 071003, China;
    2. State Grid Cangzhou Electric Power Supply Company, Cangzhou 061000, China
  • Received:2014-09-26 Online:2015-11-24 Published:2015-11-25
  • Supported by:
    National Basic Research Program of China (973 Program) (2011CB209401), the Fundamental Research Funds for the Central Universities (2014 MS92).

Abstract: In order to study the corona characteristics of aluminum conductor composite core (ACCC), corona onset tests of single ACCC-600/71 conductor and LGJ-630/45 conductor were performed based on the corona measurement system with small corona cage. The experimental result shows that: under clean and artificial smear conditions, the corona onset voltages of ACCC-600/71 conductors are higher than those of LGJ-630/45 conductor, which proves that ACCC-600/71 conductors can reduce the line losses and have good performance in energy saving and environmental protection. Surface contamination reduces the roughness factor of ACCC-600/71 and LGJ-630/45 conductors and greatly lowers the corona onset voltages. The bigger the particle size is, the higher the influence will be.

Key words: aluminum conductor composite core(ACCC), aluminum conductor steel reinforced(ACSR), corona characteristics, corona cage, corona onset voltage, roughness factor, contamination