Electric Power ›› 2019, Vol. 52 ›› Issue (7): 84-91.DOI: 10.11930/j.issn.1004-9649.201901006

Previous Articles     Next Articles

Non-uniform Pollution Method and Pollution Flashover Characteristics of Transmission Line Insulators

LIU Qin1, WANG Yiwen2   

  1. 1. China Electric Power Research Institute Co., Ltd. Wuhan Branch, Wuhan 430074, China;
    2. School of Electrical and New Energy, China Three Gorges University, Yichang 443002, China
  • Received:2019-01-10 Revised:2019-02-13 Online:2019-07-05 Published:2019-07-13
  • Supported by:
    This work is supported by Science and Technology Project of SGCC (Research on Natural Contamination Characteristics and String Length Optimization of EHV/UHV Line Insulators, No. SG11014).

Abstract: At present, pollution of insulators in artificial contamination test is done by uniform smearing, but natural pollution, affected by wind, raining, insulator shape, pollution, pollutant particle size and other factors, is a non-uniform accumulation on the insulator surface, and the non-uniform contamination has an effect on the insulator U50%. Based on a study of the natural pollution characteristics of insulators in multiple regions of a large area, different pollution characteristics of the upper and lower surfaces of different umbrella insulators are obtained, and a non-uniform artificial pollution method is proposed for the upper and lower surfaces of insulators based on the natural contamination characteristics. Non-uniform artificial contamination tests were carried out for the insulators under AC/ DC voltage, and the corresponding pollution flashover curves were obtained. The test results show that the contamination of the insulators by non-uniform pollution method is close to the actual operating conditions of insulators, and the testing results are more accurate and reasonable. It is concluded that the more non-uniform of the contamination on the upper and lower surfaces, the larger the U50% value is, but the incremental amplitude of U50% decreases and tends to be saturated. The main conclusions of this paper are of great significance for the optimization of insulator string length and type selection.

Key words: insulator, non-uniform pollution method, artificial contamination test, pollution flashover characteristics, insulation coordination

CLC Number: