中国电力 ›› 2017, Vol. 50 ›› Issue (7): 147-152.DOI: 10.11930/j.issn.1004-9649.2017.07.147.06

• 电网 • 上一篇    下一篇

半波长调谐网络安置方式研究

赵永熹1, 王松峰1, 王华昕1, 王建1, 陈爱友2, 薛天水3   

  1. 1. 上海电力学院,上海 200090;
    2. 国网山东省电力公司莱芜供电公司,山东 莱芜 271100;
    3. 国网山东省电力公司德州供电公司,山东 德州 253008
  • 收稿日期:2017-02-25 出版日期:2017-07-05 发布日期:2017-07-25
  • 作者简介:赵永熹(1979—),女,山东青岛人,博士研究生,副教授,从事特高压半波长交流输电技术研究。E-mail: zhao-yongxi@126.com
  • 基金资助:
    国家自然科学基金资助项目(51307104)

Study on the Resettlement Modes of Half-Wavelength Tuned Network of Transmission Lines

ZHAO Yongxi1, WANG Songfeng1, WANG Huaxin1, WANG Jian1, CHEN Aiyou2, XUE Tianshui3   

  1. 1. Shanghai University of Electric Power, Shanghai 200090, China;
    2. Laiwu Power Supply Company, State Grid Shandong Electric Power Corporation, Laiwu 271100, China;
    3. Dezhou Power Supply Company, State Grid Shandong Electric Power Corporation, Dezhou 253008, China
  • Received:2017-02-25 Online:2017-07-05 Published:2017-07-25
  • Supported by:
    ; This work is supported by the National Natural Science Foundation of China (No.51307104)

摘要: 当实际输电线路长度不足半波长时,需要通过人工调谐补偿。调谐网络类型需要详细论证。针对3种调谐网络,首先探索其分别适用于何种补偿方式;其次探讨适合于各调谐网络的安装和分布形式;最后对比各调谐线路过电压情况。研究表明:电容型在分散式补偿时无功过剩,PI型和T型在分散式安装方式下的过电压水平要高于集中式,线路侧补偿时的过电压水平较低。即电容型适宜采用分散式;PI型和T型调谐网络更适宜采用集中式;3种调谐网络中适宜采用安装在线路侧的集中式安置。

关键词: 半波长交流输电, 调谐网络, 补偿方式, 安装位置, 分布方式, 过电压

Abstract: When the actual length of transmission line is less than the half wavelength, the manual tuned compensation is needed. However, detailed analysis is needed to determine the appropriate tuned network types. Firstly, based on the existing three types of tuned networks, their respective suitable modes for compensation are investigated. In addition, the installation and distribution mode suitable for each tuned network is discussed. Finally, the overvoltage of each tuned transmission lines is comparatively analyzed. The results show that the reactive power is surplus when distributed compensation is used for capacitor-type tuned network; For PI and T type, the overvoltage level under distributed installation is higher than that under centralized mode, and the overvoltage level is low when line side compensation is used. Therefore, it can be concluded that the C type tuned network is suitable for the distributed compensation, while the PI and T type tuned networks are more suitable for centralized compensation; the three types of tuned networks are suitable for centralized installation on the line side.

Key words: half-wave-length AC transmission, tuned network, compensation mode, installation position, distribution mode, overvoltage