分布式电源接入城市配电网规则分析

王峥1, 梁伟1, 陈思佳2, 韩亮2, 王守相2   

  1. 1. 天津市电力公司 电力科学研究院,天津 300384; 2. 天津大学 智能电网教育部重点实验室,天津 300072
  • 收稿日期:2013-03-11 出版日期:2013-07-23 发布日期:2015-12-10
  • 作者简介:王峥(1983—),女,天津人,硕士,工程师,从事电力系统分析及其自动化方面的研究。
  • 基金资助:
    国家自然科学基金资助项目(NSFC 50837001,51077098); 国家重点基础研究发展计划(973计划)资助项目(2009CB219708); 国家高技术研究发展计划(863计划)资助项目(2011AA05A106)

Rules of Distributed Generator Integration to Urban Distribution Network

WANG Zheng1, LIANG Wei1, CHEN Si-jia2, HAN Liang2, WANG Shou-xiang2   

  1. 1. Electric Power Research Institute of Tianjin Electric Power Corporation, Tianjin 300384, China; 2. Key Laboratory of Smart Grid of Ministry of Education, Tianjin University, Tianjin 300072, China
  • Received:2013-03-11 Online:2013-07-23 Published:2015-12-10

摘要: 为减轻分布式电源接入对城市配电网产生的负面影响,国内外制定了一些分布式电源并网准则,以保证分布式电源的安全有效接入,但这些并网规则的制定依据并没有明确给出。为此,以天津城区典型的35 kV 高压、10 kV中压和400 V低压配电网为例,计算分析接入分布式电源对城市配电网线路载流量和母线电压的影响,给出分布式电源并网规则中关于接入容量和接入电压等级要求的依据,并讨论分布式电源接入配电网后对电压偏差、频率偏差、谐波及三相不平衡度等方面的电能质量的影响及其要求和依据。

关键词: 分布式发电, 并网, 配电网, 电能质量

Abstract: In order to mitigate the adverse impact of integration of distributed generators (DGs ) to distribution systems, some rules for interconnecting DGs with electric power systems are made all over the world to guarantee the safe and effective integration of DGs. However, no definite basis are given for these rules. Therefore, case studies of Tianjin distribution networks of 35 kV high voltage, 10 kV medium voltage and 400 V low voltage are conducted, and the influences of DGs on line maximum capacity and bus voltage are calculated, through which the theoretical bases of the capacity and voltage level of DG integration are obtained, and requirements for power quality of DG integration in terms of voltage deviation, frequency deviation, harmonics, and three-phase imbalance are set up.

Key words: distributed generation, integration, distribution network, power quality