Electric Power ›› 2017, Vol. 50 ›› Issue (10): 120-123.DOI: 10.11930/j.issn.1004-9649.201703014

• Generation Technology • Previous Articles     Next Articles

Effect of Low Frequency Oscillation of Power System on Operation Safety of Steam Turbine Unit

ZHANG Bao1, FAN Yinlong1, YIN Xuyang2, HU Zhou1, GU Zhenghao1   

  1. 1. State Grid Zhejiang Electric Power Research Institute, Hangzhou 310014, China;
    2. Shenhua Zhejiang Guohua Zheneng Group Power Plant Co., Ltd., Ninghai 315612, China
  • Received:2017-03-20 Online:2017-10-25 Published:2017-10-30

Abstract: The low frequency oscillation of the power system has occurred many times in China, which endangers the safe operation of the steam turbines. Based on the specific cases, the different reactions of the steam turbines during the low frequency oscillations of the power system are analyzed. It is pointed out that the low frequency oscillation of the power system is threatening the safe operation of the unit in two ways. One is the speed measurement and the other is the turbine valve opening fluctuation. Through the actual testing, it is observed that the control oil pressure of a unit declines continuously when the low frequency oscillation occurs. Taking China’s situations into account, it is suggested that measures should be taken to improve the anti-interference ability of the control oil system, and contingency plans should be made.

Key words: steam turbine, power system, low frequency oscillation, turbine governor, speed, regulating valve