Electric Power ›› 2026, Vol. 59 ›› Issue (3): 114-124.DOI: 10.11930/j.issn.1004-9649.202506024

• New-Type Power Grid • Previous Articles     Next Articles

Key parameter selection method for allocation of allowable harmonic current values

TAO Shun1(), CHEN Huilin2(), XU Yonghai1(), ZHOU Shengjun3(), XIAO Xiangning1   

  1. 1. College of Electrical and Electronic Engineering, North China Electric Power University, Beijing 102206, China
    2. Ninghai County Power Supply Company, State Grid Zhejiang Electric Power Co., Ltd., Ningbo 315600, China
    3. China Electric Power Research Institute, Beijing 100192, China
  • Received:2025-06-10 Revised:2026-01-25 Online:2026-03-16 Published:2026-03-28
  • Supported by:
    This work is supported by National Natural Science Foundation of China (No.52377101).

Abstract:

Since its promulgation and implementation, GB/T 14549 has effectively regulated the harmonic issues in power grids and ensured the power quality. However, with the development of new power systems, the harmonics in power grids have exhibited new characteristics, making GB/T 14549 hardly fully adaptable to the current needs of power grid development and modern management. Therefore, aiming at the harmonic characteristics in new power systems, and based on allocation method for allowable harmonic current values specified in GB/T 14549, this paper focuses on the constraint index for total harmonic current, the selection method for power supply capacity, and the superposition method, respectively, and proposes the selection methods for key parameters. Its rationality and effectiveness are validated through the case studies, which effectively restricts harmonic injection and provides a reference for the revision of the national harmonic standards.

Key words: GB/T 14549, total harmonic current constraint, power supply capacity, harmonic superposition