Electric Power ›› 2014, Vol. 47 ›› Issue (5): 72-77.DOI: 10.11930/j.issn.1004-9649.2014.5.72.5

• Power System • Previous Articles     Next Articles

Improving Grid Dynamic Stability by Installing SVCs in Relative Substations in Sichuan-Chongqing Power Grid of UHVAC/UHVDC

CHEN Han-xiong1, LI Lan2   

  1. 1. PCCC Sichuan Electric Power Design & Consulting Co. Ltd., Chengdu 610016, China;
    2. Sichuan Electric Power Company, Chengdu 610094, China
  • Received:2014-02-17 Online:2014-05-31 Published:2015-12-21

Abstract: In order to resolve the problem of insufficient dynamic reactive power support of the load center of Chengdu-Chongqing power grid and improve the grid dynamic stability and transfer spare hydropower from Sichuan to eastern China, the grid dynamic stability by installing SVCs in relative substations in Sichuan-Chongqing Grid of UHVAC/UHVDC was studied based on the planning of the AC-DC Sichuan-Chongqing power grid and the feasibility study of installing SVC at some relative nodes. The results show that the capacity of the AC passage can be increased by about 3 700 MW after installing SVCs with certain capacities on relative UHV notes in Chengdu and Chongqing grids by 2020.

Key words: SVC, UHVAC, UHVDC, Power System