Electric Power ›› 2019, Vol. 52 ›› Issue (4): 96-103.DOI: 10.11930/j.issn.1004-9649.201804111

Previous Articles     Next Articles

Study on Control Strategy of Back to Back MMC-HVDC Connecting Chongqing and Hubei Power Grid

FAN Yunlong1, REN Jianwen1, YE Xiaohui2, LI Xia2   

  1. 1. State Key Laboratory of Alternate Electric Power System with Renewable Energy Sources, North China Electric Power University, Baoding 071003, China;
    2. China Electric Power Research Institute, Beijing 100192, China
  • Received:2018-04-20 Revised:2018-09-10 Online:2019-04-05 Published:2019-04-16

Abstract: The construction of back to back MMC-HVDC connecting Chongqing and Hubei Power Grid has put forward higher requirements for the dynamic control capability of large-scale power grids. This paper first introduces the system structure of the project. After studying the basic MMC-HVDC control strategy, considering the demand of the actual project for the control effect on the system operation, this paper proposes a new double-loop control strategy based on the traditional power control, in which the limit of the voltage deviation is added. At the same time, the fault crossing logic of MMC-HVDC under severe AC faults is introduced. The simulation process combining control strategy and MMC-HVDC operating zone is also provided. Finally, The PSD-PSModel is used to simulate the Chongqing-Hubei system. The results verify the effectiveness and correctness of the proposed control strategy for large-scale networked projects.

Key words: fault ride through, hybrid simulation, MMC, over-limit control, power electronics control