中国电力 ›› 2016, Vol. 49 ›› Issue (3): 99-103.DOI: 10.11930/j.issn.1004-9649.2016.03.099.05

• 智能电网 • 上一篇    下一篇

遥信SOE分辨率误差分析及相关试验方法探讨

余高旺1,王振华1,王丽1,张艳超1,毕大强2   

  1. 1. 许继电气,河南 许昌 461000;
    2. 清华大学 电机系 电力系统国家重点实验室,北京 100084
  • 收稿日期:2015-10-08 修回日期:2016-04-08 出版日期:2016-03-20 发布日期:2016-04-08
  • 作者简介:余高旺(1976—),男,湖北鄂州人,高级工程师,从事电力系统保护与控制研发工作。E-mail: yugaowang21@126.com

Analysis on the SOE Error and Relevant Experimental Methods

YU Gaowang1, WANG Zhenhua1, WANG Li1, ZHANG Yanchao1, Bi Daqiang2   

  1. 1. XJ Electric Co., Ltd, Xuchang 461000, China;
    2. State Key Lab. of Power System, Dept. of Electrical Engineering, Tsinghua University, Beijing 100084, China
  • Received:2015-10-08 Revised:2016-04-08 Online:2016-03-20 Published:2016-04-08

摘要: 智能变电站的发展对测控装置遥信SOE分辨率提出了更高的要求。详细分析了测控遥信SOE分辨率在测试过程中出现的异常现象原因,即受遥信时标最小单位为毫秒的限制,理论上测控装置遥信SOE分辨率小于1 ms的要求不可能100%满足。进行阻尼振荡波的EMC试验时,利用仿真试验在理论上证明遥信SOE错误的原因是:遥信1动作后,遥信2回路中耦合进入了初值为220 V的衰减直流分量,从而导致遥信2提前动作。最后,针对阻尼振荡波试验的特点,提出了一种解耦方案,通过改变试验接线避免了遥信回路之间的影响,即遥信1和遥信2分别接入不同的电源回路。

关键词: 测控, 遥信, SOE, EMC, 差模干扰

Abstract: Development of smart substation gives rise to the high requirements on telesignal and SOE resolution of measurement & control devices. A deep analysis is made on the abnormal phenomenon occurring in the process of testing telesignal and SOE resolution of measurement & control devices. Duo to the limit of the telesignal’s time tag that the smallest unit is in millisecond level, the requirement that the measure & control device’s telesignal and SOE resolution be less than 1ms cannot be totally satisfied in theory. During testing the damped oscillation wave of EMC,the causes for the telesignal and SOE resolution error is theoretically proved by simulation, that is: a decaying DC component with the initial value of 220 V is coupled into the circuit of the telesignal 2 after the telesignal 1 acts, which results in the telesignal 2’s action in advance. Finally, according to the characteristics of damping oscillatory wave experiment, a decoupling scheme is proposed, which can avoid the interaction between the telesignal circuits by changing the testing wiring that the telesignal 1 and signal 2 are plugged into different power circuits respectively.

Key words: measure & control, telesignal, SOE, EMC, differential mode interference

中图分类号: