Research on Electricity Burn of Shorting Grounding Wires in EHV and UHV Transmission Lines

QIN Weinan, FANG Yuqun, QIAN Liqun, LIANG Jiakai, JIANG Weidong   

  1. State Grid Jinhua Power Supply Company, Jinhua 321001, China
  • Received:2018-11-21 Revised:2019-02-11 Online:2019-09-05 Published:2019-09-19
  • Supported by:
    This work is supported by Science and Technology Project of State Grid Zhejiang Electric Power Co., Ltd. (No.5211JH170008).

Abstract: Based on EMTP simulation, an analysis is made on the induced voltage and induced current of the 1 000 kV AC double circuit lines on the same tower of the Huainan-Wannan-Zhebei-Shanghai transmission project with one circuit blackout. According to the service condition of grounding wires, it is found that the main causes for grounding wire burns are the excessive induced voltage on the blackout line and the repeated arc discharge during installation of the grounding wires. Under the maximum induced voltage calculated by simulation, the arc produced in the process of installing grounding wires is studied through test, and the critical value of arc energy which can have impact on the wire and equipment is obtained. The burn problem is effectively solved by introducing arc suppression technology, which guarantees the safety of maintenance personnel.

Key words: short circuit, intelligent grounding wire, electric arc, burn, EHV and UHV, high voltage measurement technology