Electric Power ›› 2015, Vol. 48 ›› Issue (2): 55-58.DOI: 10.11930.2015.2.55

• Power System • Previous Articles     Next Articles

Research on Lightning Invasion Wave Overvoltage in Flexible DC Converter Station

LI Tianwei1, LIU Dapeng2, LEI Yuanyuan1, ZHAO Yuming1   

  1. 1. Electric Power Research Institute, CSG, Guangzhou 510080, China;
    2. Xi’an XD Power Systems Co. Ltd, Xi’an 710075, China
  • Received:2014-09-26 Online:2015-02-25 Published:2015-11-30

Abstract: To confirm the lightning insulation level of the equipment in DC yard and the cable in converter station, a electromagnetic transient simulation model is built for flexible DC transmission project, which consists of a 1~2 km long DC transmission line in the entrance segment and a converter station. The lightning stroke current is calculated based on the electrical and structural parameters of tower-insulator-conductor. The lightning current wave is simulated by applying dual-exponential function. The tower gap flashover criterion is determined according to intersection method. The lightning invasion wave overvoltage caused by main equipment and cable in DC yard is calculated with the overhead transmission line suffering lightning. The insulation level is determined through simulation for the main equipment and cable in DC yard. In addition, the simulation shows that the DC reactor plays a certain role in controlling lightning invasion overvoltage.

Key words: flexible DC transmission, overvoltage, electrical geometry model, lightning invasion wave, cable, intersection method, converter station, DC yard

CLC Number: