Electric Power ›› 2012, Vol. 45 ›› Issue (11): 32-35.DOI: 10.11930/j.issn.1004-9649.2012.11.32.3

• Generalion Technology • Previous Articles     Next Articles

Retrofit of Heating Surfaces for DG2070/17.5-Ⅱ6 Type Boiler

FANG Zhan-ling   

  1. Datang International Power Generation Co., Ltd., Beijing 100033, China
  • Received:2012-06-08 Online:2012-11-18 Published:2016-02-29

Abstract: To decrease the extra large amount of desuperheating water in the superheaters and reheaters of the subcritical natural-circulating boiler of the Model DG2070/17.5-Ⅱ6 which severely affects the security and economics of the unit, a feasible plan is put forward based on the analysis on the structural characteristics of the heat recovery surfaces, which includes reducing the heating area of the low-temperature superheaters and the low-temperature reheaters, and increasing the heating area of the economizer adequately. The plan is put into practice at a power plant, which indicates that the amount of the desuperheating water in the superheaters and the reheaters is decreased by a big margin with the security and economics of the boilers being improved.

Key words: thermal power unit, superheater, reheater, heating surface retrofit