Compensation Reactor Parameters Study of Symmetrical Voltage Applying Mode for On-site Partial Discharge Test of Ultra High Voltage Converter Transformer

XIE Qijia1, PU Ziheng2, DU Zhiye2, WANG Tao1, ZHANG Yadong2   

  1. 1. Electric Power Research Institute of Hubei Electrical Power Company, Wuhan 430077,China;
    2. School of Electrical Engineering, Wuhan University, Wuhan 430072, China
  • Received:2015-08-25 Online:2015-11-18 Published:2015-11-18

Abstract: On-site partial discharge test of Ultra High Voltage(UHV) converter transformer requires good anti-jamming measurement and response capability due to high test voltage, specific requirement and complex field environment. Under symmetrical voltage applying mode, there is large potential difference at transformer winding terminal. It is also inconvenient to adjust reactor compensation and measure voltage and current. The equivalent method of capacitance network of Ultra High Voltage converter transformer is studied. Based on on-site test results, the simulation is performed and compensation reactor parameters are obtained.This work is supported by National Basic Research Program of China (973 Program) (No. 2011CB209404).

Key words: UHV, converter transformer, partial discharge, symmetrical voltage applying, equivalent method of capacitance, reactor