Interference Analysis of Power Frequency Parameter Measurement for 1 000 kV Wanan-Zhebei UHV Transmission Line

MA Yue1, LI Guoman1, WANG Shaohua2, CUI Zhuye3, JIN Yongtao2, JIANG Jianling2   

  1. 1. AC Project Construction Branch, State Grid Corporation of China, Beijing 100140, China;
    2. State Grid Zhejiang Electric Power Research Institute, Hangzhou 310014, China;
    3. Hangzhou Yineng Power Technology Co., Ltd., Hangzhou 310014, China
  • Received:2014-11-08 Online:2015-11-24 Published:2015-11-25

Abstract: Interference analysis of power frequency parameter measurement of UHV transmission line is an important basis for selecting appropriate anti-interference test method and analyzing the testing result. The interference voltage signals of 1 000 kV Wannan-Zhebei UHV transmission line were tested during measuring the positive sequence and zero sequence parameters, and their spectrum characteristics was analyzed. On this basis, the field testing error of positive sequence parameters was also analyzed. The results show that the interference voltage has unbalance and time-variant features. Some difference exists between the power frequency parameter testing result obtained by power frequency method and that by variable frequency method. When the interference voltage is time-varied, the variable frequency method should be adopted to measure the power frequency parameter of transmission line.