Analysis of Differential Protection Characteristic for On-Load-Tap-Changer Transformer of UHV

LI Yan-jun1, ZHOU Chun-xia1, XIAO Yuan-qing2, GUO Xiao3   

  1. 1. China Electric Power Research Institute, Beijing 100192, China;
    2. Beijing Sifang Automation Co., Ltd., Beijing 100085, China;
    3. Guodiain Nanjing Automation Co., Ltd., Nanjing 210003, China
  • Received:2014-01-10 Online:2014-09-18 Published:2015-12-10

Abstract: In order to investigate the differential protection characteristics for on-load-tap-changer transformers of UHV, the basic performances of differential transformer protection and its unbalanced differential current were studied, by which it is found that the conventional protection of on-load-tap-changer transformers may have a potential risk during the transformer tap adjustment. Through the further analysis of the influencing factors on the characteristics of unbalanced differential current, suggestions about the selection of rated current of differential protection for on-load-tap-changer transformers were proposed. In addition, the differential current distribution during the transformer tap adjustment is obtained by the simulation and the setting strategy is accordingly provided, which is also validated by the simulation.

Key words: voltage-regulating transformer, differential protection, rated current, setting strategy, UHV, simulation test, gear, differential current