Electric Power ›› 2014, Vol. 47 ›› Issue (2): 90-93.DOI: 10.11930/j.issn.1004-9649.2014.2.90.3

• Orginal Article • Previous Articles     Next Articles

Application of Electronic Instrument Transformer in Differential Protection of Electromotor

QIAN Li-hong1, WANG Wei1, WANG Ying-nan2, REN Zhe2, JIN Peng2   

  1. 1. College of Electrical Engineering, Beijing Jiaotong University, Beijing 100044, China;
    2. Shenyang Power Supply Corporation, Shenyang 110003, China
  • Received:2013-09-08 Online:2014-02-28 Published:2015-12-18

Abstract: The paper analyzes the causes of differential protection malfunction of electromotors through actual cases, elaborates the improved method of the traditional electromagnetic current transformer circuit, and introduces its defects. It is proposed in this paper to apply the electronic current transformer to the electromotor’s differential protection to prevent malfunction of protection caused by core saturation. Experiments show that the proposed scheme can effectively solve the malfunction of protection caused by core saturation, and improve the reliability and safety of electromotor’s protection.

Key words: electromotor, differential protection, magnetic saturation, electronic current transformer

CLC Number: