Electric Power ›› 2025, Vol. 58 ›› Issue (2): 133-139.DOI: 10.11930/j.issn.1004-9649.202404055

• Data-Driven Analysis and Control of Power System Security and Stability • Previous Articles     Next Articles

New Solution for Photovoltaic Station Collector Line Protection Based on Comprehensive Harmonic Drive

Jiandong WO1(), Wulue PAN2(), Yuehui LI1(), Jiayi WU2()   

  1. 1. State Grid Zhejiang Jinhua Power Supply Co., Ltd., Jinhua 321000, China
    2. State Grid Zhejiang Electric Power Co., Ltd., Hangzhou 310000, China
  • Received:2024-04-11 Accepted:2024-07-10 Online:2025-02-23 Published:2025-02-28
  • Supported by:
    This work is supported by National Natural Science Foundation of China (No.52077120), Science and Technology Project of State Grid Zhejiang Electric Power Co., Ltd. (No.5211JH230001).

Abstract:

A new protection scheme for the collection line of photovoltaic power station based on comprehensive harmonic drive is proposed. Firstly, the harmonic sources and characteristics of the collection line fault in photovoltaic power station are analyzed, and the current harmonics are obtained by fiber optical current transformer (FOCT), and the harmonic characteristic weight is calculated based on the nondominated sorting genetic algorithm Ⅱ (NSGA-Ⅱ) to improve the comprehensive harmonic characteristic of fault current. At the time, the high-order harmonic start-up criterion and the comprehensive harmonic action criterion are constructed. The simulation study is carried out for different fault conditions, and the effectiveness of proposed method is verified.

Key words: photovoltaic power station, collector line, transient characteristics, harmonic protection