Electric Power ›› 2019, Vol. 52 ›› Issue (9): 79-85.DOI: 10.11930/j.issn.1004-9649.201808041

Previous Articles     Next Articles

Operation Analysis of Over-Excitation Protection due to Voltage Transformer Inter-turn Short-Circuit at Generator Terminal

WANG Xing   

  1. China Datang Corporation Science and Technology Research Institute Co., Ltd., East China Electric Power Test and Research Institute, Hefei 230031, China
  • Received:2018-08-08 Revised:2019-03-01 Online:2019-09-05 Published:2019-09-19

Abstract: A number of inter-turn short-circuit accidents have occurred in recent years in the primary winding of voltage transformer (TV) at generator terminal, which often causes slow fuse melting due to the large short-circuit current. In this paper, a calculation formula of TV secondary winding voltage is derived respectively for TV's primary winding inter-turn short-circuit and slow fuse melting, and it is concluded that the secondary winding voltage will decrease after a fault occurs. An analysis is made on the bugs in the TV disconnection logic in ABB Unitrol F excitation regulator, and a study is conducted on the mechanism of over-excitation protection and strong excitation of the excitation regulator caused by slow fuse melting. The theory is verified through a case study of an accident. Finally, the Matlab/Simulink simulation is used to verify the theory, and the simulation result proves the correctness of the theory.

Key words: voltage transformer, inter-turn short-circuit, slow fuse melting, TV disconnection, excitation regulator