Affecting Factors of Short-Circuit Currents of Busbar at UHV AC Substation

TANG Jinrui1, YANG Fanqi1, HOU Tingting2, HUANG Juanjuan3, SHAO Chong3, WU Xiaoshan4   

  1. 1. School of Automation, Wuhan University of Technology, Wuhan 430070, China;
    2. Economics & Technology Research Institute, State Grid Hubei Electric Power Co., Ltd., Wuhan 430077, China;
    3. Central Southern China Electric Power Design Institute Co., Ltd. of CPECC, Wuhan 430071, China;
    4. Research Institute Co., Ltd. of China Southern Power Grid, Guangzhou 510080, China
  • Received:2018-04-16 Revised:2018-08-08 Online:2019-04-05 Published:2019-04-16
  • Supported by:
    This work is supported by the National Natural Science Foundation of China (No.51607130).

Abstract: The affecting factors of short-circuit currents of 1 000 kV and 500 kV bus-bar at UHV AC substation are analyzed based on the components of corresponding self-impedance. And then the proportions of all factors to the short-circuit currents at 1 000 kV bus-bar and 500 kV bus-bar are proposed and determined, including the configuration of 1 000 kV power grid, the main transformer and the configuration of 500 kV power grid. The results indicate that the short-circuit currents of 1 000 kV bus-bar are greatly affected by the configuration of 1 000 kV power grid. The 500 kV power grid and the main transformer have a dominant influence on the short-circuit currents of 500 kV bus-bar at UHV AC substation. The results can provide theoretical support and decision-making reference for the optimization of short-circuit limit.

Key words: UHV, AC substation, short-circuit current, self-impedance, equivalent circuit