Electric Power ›› 2019, Vol. 52 ›› Issue (5): 83-88,163.DOI: 10.11930/j.issn.1004-9649.201711201

Previous Articles     Next Articles

Research on Passive Wireless Temperature Measurement System of High Voltage Isolating Switch Based on Pt Resistor

HE Yanmiao1, LI Yujie2, LI Zhibing1, GAO Shan2, YANG Jinggang2, LI Hongtao2, YANG Peng3   

  1. 1. China Electric Power Research Institute, Beijing 100192, China;
    2. State Grid Jiangsu Electric Power Company Research Insitute, Nanjing 211103, China;
    3. Shandong Zhiyang Electric Co., Ltd., Zibo 255086, China
  • Received:2017-11-25 Revised:2018-05-11 Online:2019-05-05 Published:2019-05-14
  • Supported by:
    This work is supported by Science and Technology Project of SGCC (No.SGTYHT/15-JS-191).

Abstract: The online temperature measurement technology is analyzed and verified in this paper based on power supplied by the inductive current and wireless communication technique combined with the structure and principle of disconnector, solving problems in the online temperature measure system such as wireless data transmission, sensor operating supply and equipment high reliability in an environment of high voltage and strong electromagnetic. The temperature distribution of disconnector contact is analyzed in this paper under different influential factors by means of numerical simulation calculation of temperature field and temperature rise test. Contact materials of various kinds, loop resistance in defect situation as well as the corresponding relation between loop resistance and contact temperature are designed in this paper. The temperature real-time monitoring technology with low cost and high efficiency is researched in this paper. Defects of abnormal heating are discovered in time, which is of great significance for ensuring the safe operation and improving power distribution reliability.

Key words: high voltage disconnectors, Pt resistance, passive wireless, real-time monitoring, temperature measurement system

CLC Number: