Research on Bently 3500 Signal Distortion in the TSI System of 300-MW Power Generation Units

JIANG Liewei   

  1. Shaoguan Power Plant of Guangdong Province, Shaoguan 512132, China
  • Received:2016-07-07 Online:2017-01-20 Published:2017-01-23

Abstract: Aiming at the fault of frequent bearing vibration signal interruption in a 300-MW power generation unit, through the analysis on bearing current and voltage testing, vibration signal detection and control loop testing, it is verified that a clear interference signal is added to the bearing vibration signal through the cables or the network due to the ill TSI system grounding, which makes the working voltage of the eddy current sensor exceed the normal range (-2.75~-16.75 V), causing the card staying at NOT OK status and the bearing vibration signal being interrupted. Therefore, the TSI grounding network is reconstructed. Since the completion and application of the network no abnormal bearing vibration signals have ever appeared. Thus, the unit security has been greatly improved.

Key words: thermal power plant, turbine supervisory instrumentation(TSI), Bently 3500, bearing vibration, grounding, interference, eddy current sensor