Electric Power ›› 2014, Vol. 47 ›› Issue (4): 48-51.DOI: 10.11930/j.issn.1004-9649.2014.4.48.3

• Orginal Article • Previous Articles     Next Articles

Optimization Tests on Main Steam Pressure for 600-MW Air-Cooling Heat Supply Units

WANG Jin-quan1, LI Jun2, LU Hong-kai2   

  1. 1. Shanxi Gemeng Safety Production Consultation Co. Ltd., Taiyuan 030000, China;
    2. Shanxi Zhaoguang Power Generation Co. Ltd., Huozhou 031400, China
  • Received:2013-12-26 Online:2014-04-30 Published:2015-12-22

Abstract: The variation of steam extraction volume and exhaust pressure with main steam pressure is studied through the tests on the 600-MW air-cooling heat supply units and the quantitative measurement on the changes of the heat consumption rate under the conditions of different extraction volumes and exhaust pressures is conducted. The year-around efficient fixed and sliding pressure operation model is put forward and the original unit sliding pressure operation logic is modified. The operation results show that a decrease of net coal consumption of 1.1 g/(kW·h) can be obtained when the sliding pressure curve is at the loads of 450 MW and the heating steam extraction is 300 t/h.

Key words: air-cooling unit, heat supply unit, sliding pressure operation, heating extraction, exhaust pressure, optimal operation