journal1 ›› 2015, Vol. 48 ›› Issue (8): 80-85.DOI: 10.11930/j.issn.10.11930.2015.8.80

• Power System • Previous Articles     Next Articles

Study on On-Line Monitoring Index of MOA

CAO Hongliang12, YANG Zhongjiang12, REN Jing3, JIANG Su12, LI Pengfei12   

  1. 1. Key Laboratory for Aerosol-Cloud-Precipitation of China Meteorological Administration, Nanjing University of Information Science & Technology, Nanjing 210044, China;
    2. School of Atmospheric Physics, Nanjing University of Information Science and Technology, Nanjing 210044, China;
    3. Ningbo Air Traffic Manage Station of Civil Aviation, Ningbo 315154, China
  • Received:2015-02-22 Online:2015-11-25 Published:2015-08-25
  • Supported by:
    National Key Basic Research Program of China (973 Program) (No. 2014CB441405); and by National Natural Science Foundation of China (No. 41075025).

Abstract: The metal oxide arrester (MOA) plays a very important role in the safe operation of power systems. In order to find an appropriate indicator that can reflect the degradation of MOA, a comparative study is made through Matlab simulation on the existing fundamental harmonic resistant current and the third harmonic resistant current. The result shows that the resistant current with fundamental harmonic component and the third harmonic component produced by the fundamental voltage can better reflect the degradation of MOA. In addition,based on Fryze’s power definition, a simple algorithm which can calculate the fundamental harmonic current produced by the fundamental voltage is proposed and its efficiency is validated by simulation.

Key words: MOA, online monitoring, index, harmonic voltage, fundamental harmonic resistant current, capacitive current

CLC Number: