Analysis on the Unbalanced Circuit Current of the 3/2 Wiring System of 1 000 kV UHV Nanyang Substation

LIU Tao1, FANG Jinyan2, CHENG Chaolei1, HUANG Jianjin1, XU Ruina1   

  1. 1. Maintenance Company of Henan Electric Power Corporation, Zhengzhou 450051, China;
    2. Jiangxi Electric Power Dispatch & Control Center, Nanchang 330077, China
  • Received:2014-09-26 Online:2015-11-24 Published:2015-11-25

Abstract: 3/2 main wiring is used in the 1 000 kV system of UHV AC substation. Since the resistive unbalance in the main conductive circuit is significant and the power transmission capacity is large, unbalanced circulation exists in the 3/2 wiring system. In extreme case, some breakers’ single-phase current appears zero or even phase-inverted. Based on the UHV Nanyang substation, the zero-sequence of the unbalanced circulation and the cause are theoretically analyzed. The serious problems and consequences of the secondary system caused by zero-sequence circulation during large load operation are discussed and several solutions are proposed: the conflux current of two breakers is used for protection device; the minimum current of 3-phase brakes the zero-sequence module in single breaker; the conflux current of two breakers brakes single breaker zero-sequence module. This analysis is expected to call enough attention to be paid to the unbalanced circulation in the future projects.

Key words: UHVAC, UHVAC substation, main conductive circuit, resistive unbalanced, unbalanced circuit, zero-sequent circuit