Electric Power ›› 2018, Vol. 51 ›› Issue (4): 53-60.DOI: 10.11930/j.issn.1004-9649.20160145

Previous Articles     Next Articles

Analytical Method of GIS Faults Based on Ultrasonic Diagnosis

ZHOU Dianbo1, DING Dengwei1, GAI Shicheng2, JIA Zhijie1, WANG Jie1, MA Xiaomin1, YAO Chenguo3   

  1. 1. State Grid Sichuan Electric Power Research Institute, Chengdu 610072, China;
    2. State Grid Sichuan Maintenance Company, Chengdu 610042, China;
    3. State Key Laboratory of Power Transmission Equipment & System Security and New Technology, Chongqing University, Chongqing 400030, China
  • Received:2016-03-02 Revised:2017-12-09 Online:2018-04-05 Published:2018-04-12

Abstract: To improve on-site detection efficiency of partial discharge of gas insulated switchgear (GIS), a study is made in this paper on the analytical methods of GIS fault based on ultrasonic diagnosis. According to plenty of data collected on site, the time domain and phase distribution features of ultrasonic signals of typical GIS partial discharge are analyzed, and the differences in time domain features and frequency domain distribution between partial discharge signals and mechanical vibration signals are identified. The paper also studies the application of the joint ultrasonic and electromagnetic wave localization method, the ultrasonic time-delay localization method, and the ultrasonic wavelet time-frequency localization method in on-site GIS partial discharge detection. The detecting results indicate that the proposed methods are reliable in accuracy and correctness.

Key words: ultrasonic, gas insulated switchgear, partial discharge, time domain features, frequency domain distribution, localization method

CLC Number: