Electric Power ›› 2021, Vol. 54 ›› Issue (8): 19-26.DOI: 10.11930/j.issn.1004-9649.202006235

Previous Articles     Next Articles

High Frequency Resonance Frequency Shift Method for Cable Distribution System

ZHU Mingxing1, KONG Binbin1, ZHANG Huaying2   

  1. 1. School of Electrical Engineering and Automation, Anhui University, Hefei 230601, China;
    2. Shenzhen Power Supply Co., Ltd., Shenzhen 518000, China
  • Received:2020-06-28 Revised:2020-12-18 Online:2021-08-05 Published:2021-08-05
  • Supported by:
    This work is supported by Science and Technology of Shenzhen Power Supply Co., Ltd. (No.090000KK52180063)

Abstract: In order to solve the problem of high frequency resonance in cable distribution network, a high frequency resonance frequency shift method based on impedance reconstruction of distribution network is proposed. Firstly, an analysis is made of the mechanism of high frequency harmonic source and high frequency resonance in cable distribution network. Secondly, a high frequency resonance frequency shift method is proposed for impedance reconstruction of cable distribution network, and the frequency shift and resonance peak suppression effects are compared after reconstruction of different passive impedances. And then, based on actual project cases, the high frequency resonance suppression effects of the proposed method and its impact on the system stability are evaluated using the Bode diagram and root locus plotted with the system function, and the effectiveness of the proposed method is verified. Finally, the influence of passive impedance parameters on high frequency resonance of distribution network is studied.

Key words: cabling, high frequency resonance frequency shift, impedance reconstruction, Bode diagram, root locus