Electric Power ›› 2016, Vol. 49 ›› Issue (10): 60-66.DOI: 10.11930/j.issn.1004-9649.2016.10.060.07

• Power System • Previous Articles     Next Articles

Transient Temperature Calculation of Buried Cable Core Based on Parameter Fitting of Thermal Circuit

HUANG Xiongfeng1, XU Binzhao2, ZHANG Yujiao2, CUI Houkun3, WANG Tinghua3, AN Zengjun3   

  1. 1. Hubei Micro-grid Engineering Technology Research Center China Three Gorges University, Yichang 443002, China;
    2. College of Electrical Engineering and New Energy, China Three Gorges University, Yichang 443002, China;
    3. State Grid Jiangsu Electric Economic Research Institute, Nanjing 210008, China
  • Received:2016-03-10 Online:2016-10-10 Published:2016-11-07
  • Supported by:
    This work is supported by The National Natural Science Foundation of China (No. 51207081).

Abstract: Transient temperature calculation of buried cable is of great importance in distribution capacity distribution and security warning. However, in practice thermal parameters of insulation material and surrounding soil are either difficult to obtain or subject to slow variations due to aging effects. Those lead to inaccurate cable temperature calculation results by means of numerical calculation or traditional equivalent thermal circuit. A thermal circuit based approach is proposed by fitting equivalent thermal circuit parameter with trust-region algorithm when the station and laying environment of the cable is known. A simplified formula is deduced to avoid parameter acquisition difficulty and reduce calculation complexity. The temperature-rise experiment data of a 110 kV cable proves validity of proposed method.

Key words: parameter fitting, transient calculation, thermal circuit, trust region