Electric Power ›› 2013, Vol. 46 ›› Issue (4): 43-47.DOI: 10.11930/j.issn.1004-9649.2013.4.43.4

• Power System • Previous Articles     Next Articles

Calculation and Analysis on Electromagnetic Coupling Component of AC/DC Transmission Lines on the Same Tower Built in Same Corridor

WU Chi1, ZHANG Long-wei2, ZHU Jun2, WU Guang-ning2, SHI Chao-qun2, WU Jing-wen2   

  1. 1. Sichuan Electric Power Research Institute, Chengdu 610031, China;
    2. School of Electrical Engineering, Southwest Jiaotong University, Chengdu 610031, China
  • Received:2013-01-12 Online:2013-04-05 Published:2015-12-14

Abstract: To make full use of the overhead line corridor, development of AC/DC transmission lines on the same tower will be a future trend for power grid. It is therefore of great significance to study the electromagnetic coupling interference of AC/DC transmission lines on the same tower. The coupling model of double-circuit AC and single-circuit DC transmission lines was established based on PSCAD/EMTDC in this paper. The results show that the electromagnetic coupling component of DC lines are smaller when AC lines are arranged in inverted triangle and the phase conductors are arranged in ABC/ACB. The balance of electrical parameters are severely damaged by AC lines fault, leading to the increasing of electromagnetic coupling component of DC lines. The more the coupling ground wires are, the better the shielding effect is. The shielding effect tends to saturation when the number of coupling ground wires reaches a certain number.

Key words: AC/DC on the same tower, electromagnetic coupling, arrangement, line fault, coupling ground wires, PSCAD/EMTDC

CLC Number: