中国电力 ›› 2021, Vol. 54 ›› Issue (11): 91-96,114.DOI: 10.11930/j.issn.1004-9649.202105071

• 基于电力电子装备的配电网运行控制与形态演变专栏 • 上一篇    下一篇

基于邻接矩阵的低压配电网故障区段定位方法

姚永峰1, 王启哲2, 王慧萍1, 贾佳1, 夏西宾1   

  1. 1. 国网河南省电力公司新乡供电公司, 河南 新乡 453000;
    2. 武汉大学 电气与自动化学院, 湖北 武汉 430072
  • 收稿日期:2021-05-18 修回日期:2021-09-14 出版日期:2021-11-05 发布日期:2021-11-16
  • 作者简介:姚永峰(1976-),男,硕士,高级工程师,从事配电网规划和管理研究,E-mail:yyffzw@163.com;王启哲(1997-),男,通信作者,硕士研究生,从事有源配电网运行控制技术研究,E-mail:1249904433@qq.com;王慧萍(1976-),女,硕士,从事电网建设项目管理及其运行维护研究,E-mail:1412208227@qq.com
  • 基金资助:
    国家自然科学基金资助项目(考虑限流型能量路由器的微网群故障穿越协调控制研究,51877154)。

Faulted Line Segment Location Method for Low-Voltage Distribution Network Based on Adjacency Matrix

YAO Yongfeng1, WANG Qizhe2, WANG Huiping1, JIA Jia1, XIA Xibin1   

  1. 1. State Grid Henan Electric Power Company Xinxiang Power Supply Company, Xinxiang 453000, China;
    2. School of Electrical Engineering and Automation, Wuhan University, Wuhan 430072, China
  • Received:2021-05-18 Revised:2021-09-14 Online:2021-11-05 Published:2021-11-16
  • Supported by:
    This work is supported by National Natural Science Foundation of China (Research on Coordinated Fault Traversal Control of Microgrid Group Considering Current Limiting Energy Router, No.51877154)

摘要: 低压配电网具有线路区段短、分支众多且拓扑结构复杂多变的特点,分布式电源的并网进一步增加了其故障定位的难度。结合图论分析方法和人工智能算法,提出了基于拓扑邻接矩阵的低压配电网故障区段定位方法。首先生成与配电网故障监测单元配置相对应的邻接矩阵,其次建立故障电流在故障监测单元拓扑中的连通性等效模型,根据故障电流从电源到估计故障区段的最短路径计算故障监测信息。以此为基础建立了考虑多重故障的低压配电网故障定位模型并利用粒子群优化算法进行模型求解。仿真算例验证了所提方法能够有效提高故障定位的效率和准确度。

关键词: 低压配电网, 故障区段定位, 邻接矩阵, 最短路径, 粒子群算法

Abstract: The low-voltage distribution network is characterized by short feeder line sections, a large number of line branches, and a complex and changeable topology, and the integration of distributed generation further complicates the faulted line segment location problem. This paper investigates a novel faulted line segment location algorithm by combining the graph theory and artificial intelligence algorithm. Firstly, the adjacency matrix corresponding to the configuration of the fault monitoring units in distribution network is built, then the connectivity equivalent model of fault current in the topology of fault monitoring units is established. The monitoring information of the fault monitoring unit is calculated according to the shortest path from the power source to the estimated fault line section. Based on these works, the fault line segment location model of low-voltage distribution network considering multiple faults is developed, and the particle swarm optimization algorithm is used to solve the model. The results of simulation examples show that the proposed method can effectively improve the efficiency and accuracy of fault location.

Key words: low-voltage distribution network, fault section location, adjacency matrix, the shortest path, particle swarm optimization algorithm