Cause Analysis on Steam Turbine Valve Control Misoperation during Grid Instantaneous Faults

ZHANG Bao1, YANG Tao1, XIANG Jin1, FAN Yin-long1, GU Zheng-hao1, XU Feng2, LIU Xiao-sheng1   

  1. 1. Zhejiang Electric Power Research Institute of State Grid Corporation, Hangzhou 310014, China;
    2. Zheneng Yueqing Power Generation Co., Ltd., Yueqing 325609, China
  • Received:2013-10-09 Online:2014-05-31 Published:2015-12-21

Abstract: In this paper, several steam turbine fast valve control misoperation events caused by grid instantaneous failures are introduced. In combination with the grid fault record data, several power transmitters of different types are tested. The result shows that when the input signal changes rapidly, distortion happens in the output value of some power transmitters with the distortion direction and amplitude relevant to the phase of faults, fault time, power transmitter connection type and the manufacturer such that the grid fault information may be amplified, which is the root cause of the fast valve control misoperation events. Based on the test results, some suggestions are put forward on the selection and application of power transmitters.

Key words: steam turbine, fast valve control, transient grid interruption (KU), power load unbalance (PLU), power transmitter