Simulation Analysis of Breakdown Characteristics in Isolation Switch Fracture in Same Frequency and Phase AC Withstand Voltage Test of 110 kV Three-Phase Cylindrical GIS

QIN Yifan1,2, NIU Zheng2, SUN Yunsheng2, ZHENG Yibo1,2, NING Linru1,2, WU Haotian3, LI Xuebao3   

  1. 1. State Grid Jibei Electric Power Research. Institute, Beijing, 100045, China;
    2. State Grid Jibei Electric Power Co., Ltd., Beijing, 100032, China;
    3. North China Electric Power University, Beijing, 102206, China
  • Received:2019-12-13 Revised:2020-02-20 Published:2021-07-12
  • Supported by:
    This work is supported by Manages Science and Technology Projects in State Grid Jibei Electric Power Co., Ltd. (No.52010117000M)

Abstract: The same frequency and phase AC withstand voltage test technology has been widely used in the insulation performance test of inspection or expansion in 220kV Gas Insulated Switchgear (GIS), which can avoid stopping running grid bus of the system. However, the technology has been promoted in the withstand voltage test of GIS equipment with 110 kV voltage level. The three-phase cylindrical structure is generally adopted in 110 kV GIS devices. Due to the small inter-phase space, the switch has a higher risk of breakdown when the three-station disconnecting switch is subjected to the withstand voltage test. In this paper, the EMTP-ATP simulation software is used to construct the breakdown model of 110 kV GIS equipment in the same frequency and phase AC withstand voltage test. The fault voltage and current characteristics of the same phase and wrong phase is obtained. The influence of the installation protection resistances on the breakdown characteristics is analyzed, and the suggestions for suppression of the breakdown characteristics are given. This paper can provide useful references for the application of the same frequency and phase technology in the AC withstand voltage test of 110 kV GIS equipment.

Key words: GIS equipment, same frequency and phase, AC withstand voltage test, breakdown