封闭煤场中煤堆温度传递特性试验研究

王欢,周永刚,李培,王炳辉,赵虹   

  1. 浙江大学能源清洁利用国家重点试验室,浙江 杭州 310027
  • 收稿日期:2015-02-16 出版日期:2015-05-25 发布日期:2015-11-27
  • 作者简介:王欢(1992—),男,江苏盐城人,硕士研究生,从事封闭煤场经济安全性储存研究。E-mail: 21427011@zju.edu.cn

Experimental Research on Temperature Transfer Characteristics of Coal Pile in Closed Coal Yard

WANG Huan, ZHOU Yonggang, LI Pei, WANG Binghui, ZHAO Hong   

  1. State Key Laboratory of Clean Energy Utilization, Zhejiang University, Hangzhou 310027, China
  • Received:2015-02-16 Online:2015-05-25 Published:2015-11-27

摘要: 封闭煤场因具有对周围环境污染小、可避免恶劣天气对储煤场安全运行的影响等优点成为燃煤电厂新型储煤型式之一。通过模拟封闭煤场中的储煤堆,研究其温度的传递特性。试验结果表明,热源上侧温度传递最剧烈,其次是左右两侧,下侧的温度传递最缓慢。随煤样全水分的降低,水分对煤样温度传递的影响降低。随热源温度的降低,热源周围温度传递的不均匀性降低。因此,布置温度测点时高温区域下方的测点应相对较密且报警温度应低于上方的报警温度。

关键词: 封闭煤场, 热源点, 温度传递, 均匀性

Abstract: The closed coal yard has become the new style of coal storage in coal-fired power plants thanks to its advantages of less pollution to the environment and capabilities of maintaining coal yard safe operation during bad weathers, etc. In this paper, the coal heap of the closed coal yard is simulated to study the heat transfer characteristics. The experiment results show that on the upper side of the heat source point, the heat transfer is the strongest, and in the left and right side areas it is next to the upper side, while it is the weakest in the lower side area. Moreover, with the total moisture in the coal sample reduced, the impact of moisture on temperature transfer characteristics weakens. When the temperature of the heat source point is lowered, the unevenness of the temperature transfer around the heat source point is alleviated. Therefore, more thermometers should be installed below the high-temperature area, and the alarm temperature in the lower side area of the heat source should be set lower than that in the upper side area.

Key words: closed coal yard, heat source point, heat transfer, uniformity