中国电力 ›› 2019, Vol. 52 ›› Issue (5): 113-118.DOI: 10.11930/j.issn.1004-9649.201805006

• 电网 • 上一篇    下一篇

±800 kV宾金线浙江段正负地闪多重回击特征分析

周路遥, 李特, 王少华, 刘黎, 胡文堂, 周象贤   

  1. 国网浙江省电力公司电力科学研究院, 浙江 杭州 310014
  • 收稿日期:2018-05-03 修回日期:2018-08-08 出版日期:2019-05-05 发布日期:2019-05-14
  • 作者简介:周路遥(1992-),男,硕士,从事输电设备状态监测分析及状态评价技术研究工作,E-mail:314146873@qq.com
  • 基金资助:
    国网浙江省电力公司科技项目(5211DS16002P)。

Multiple Return-Stroke Characteristics for Positive and Negative Cloud-to-Ground Lightening of ±800 kV Binjin Line Corridor in Zhejiang Province

ZHOU Luyao, LI Te, WANG Shaohua, LIU Li, HU Wentang, ZHOU Xiangxian   

  1. State Grid Zhejiang Electric Power Research Institute, Hangzhou 310014, China
  • Received:2018-05-03 Revised:2018-08-08 Online:2019-05-05 Published:2019-05-14
  • Supported by:
    This work is supported by Science and Technology Program of State Grid Zhejiang Electric Power Company (No.5211DS16002P).

摘要: 为得到±800 kV宾金线浙江段沿线走廊正、负地闪多重回击特征,对2017年6月至9月监测到的3 032例完整地闪样本的特征参数进行了统计分析,主要包括回击次数、地闪持续时间、回击间隔时间、回击强度四个方面。多重回击参数呈明显的随回击序号系统性变化特征,且正、负地闪特性差异较为明显。统计结果表明:正、负地闪样本数量分别占27.57%和72.43%;负地闪样本中单回击占52.60%,最大回击次数达到13次,平均回击次数为2.47次;正地闪样本中单回击占比更大,达到77.04%,而回击次数相对较少,其最大回击次数为5次,平均回击次数仅为1.26次。正、负地闪多重回击持续时间随回击次数增加呈递增趋势,且负地闪持续时间的增长速度更快,其整体的算术平均分别为250.20 ms和343.02 ms。负地闪回击间隔时间随回击次序变化不明显,而正地闪回击间隔时间随回击次序呈递减趋势。总体上正、负地闪后续回击强度比值均随后续回击次序增加呈递减趋势;负地闪首次回击电流强度随回击次数增加呈递增趋势,而正地闪变化趋势不明显。

关键词: 特高压直流, 多重回击, 地闪特征, 回击次数, 回击间隔, 回击强度

Abstract: In order to obtain the multiple return-stroke characteristics of positive and negative cloud-to-ground lightening in the corridor of the ±800 kV Binjin line in Zhejiang province, the statistical parameters of the 3 032 cloud-to-ground lightening samples monitored from June to September 2017 are statistically analyzed, including return-stroke times, cloud-to-ground lightening duration, return-stroke time interval, and return-stroke intensity. The multiple return-stroke parameters show obvious systematic variations with the return-stroke number, and the difference between positive and negative return-stroke characteristics is obvious. The statistical results show that the number of positive and negative lightening samples accounted for 27.57% and 72.43%, respectively. Single return-stroke account for 52.60% of negative lightening samples. The maximum number of return-stroke reaches 13, and the average number of return-stroke is 2.47. Single return-stroke account for 77.04% of positive lightening samples, and the number of return-stroke is relatively small. The maximum number of return-stroke is 5 and the average number is only 1.26. The durations of multiple return-stroke for positive and negative lightening are both positively correlated with the number of return-stroke and the overall arithmetic mean values are 250.20 ms and 343.02 ms, respectively. The negative return-stroke time interval does not vary significantly with the return-stroke order, while the positive one decreases with the return-stroke order. Overall, subsequent return-stroke intensity ratios of positive and negative lightening decrease with the subsequent return-stroke order. The first return-stroke current intensity of negative lightening increases with the number of return-stroke, while the trend of positive lightening is not obvious.

Key words: UHVDC, multiple return-stroke, cloud-to-ground lightening characteristics, return-stroke times, return-stroke time interval, return stroke intensity