高级检索

基于去趋势分析的大规模双馈风电场送出变压器差动保护

Differential Protection of Transmission Transformer for Large-Scale Doubly-Fed Wind Farms Based on Detrended Analysis

  • 摘要: 由于双馈风电场输出的故障电流具有频偏特性且含有较大的谐波分量,当双馈风电场送出变压器发生内部故障时,变压器差动电流中二次谐波与基波的比值增大,使得变压器差动保护面临延时动作的风险;且系统发生故障时,双馈风电场输出的故障电流中存在大量非周期分量,会使得送出变压器中的电流互感器更易发生饱和现象,致使传统变压器差动保护的可靠性降低。提出了基于去趋势分析的大规模风电场送出变压器的差动保护方案。首先,将采样电流通过滑动数据窗进行去趋势分析得到去趋势残差函数,然后,结合电流波形斜率特征完成对变压器励磁涌流及故障差流(包含电流互感器饱和状态下)的有效区分。最后,在PSCAD中搭建了双馈风电场送出系统,在不同工况下验证且分析了所提保护方案的适用性。

     

    Abstract: Since the fault current output from the doubly-fed wind farm has frequency deviation characteristics and contains large harmonic components, when an internal fault occurs in the transmission transformer for the doubly-fed wind farm, the ratio of the second harmonic to the fundamental wave in the differential current of the transformer increases, which makes the differential protection of the transformer face the risk of delay action. Moreover, when the system fails, a large number of non-periodic components in the fault current output from the doubly-fed wind farm will make the current transformer in the transmission transformer more prone to saturation, resulting in reduced reliability of the differential protection of traditional transformers. This paper proposes a differential protection scheme for the transmission transformer for large-scale wind farms based on detrended analysis. Firstly, the sampling current is processed by detrended analysis through the sliding data window to obtain the detrended residual function, and then the slope characteristics of the current waveform are utilized to complete the effective distinction between the magnetizing inrush current and the fault differential current (including the current transformer saturation state) of the transformer. The proposed protection scheme is validated to be applicable under different operating conditions by building a transmission system for the doubly-fed wind farm in PSCAD.

     

/

返回文章
返回